40 CFR Part 63, Table 31

Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov
Tank diameter D (feet) bNo. of vacuum breakers, NF6No. of roof drains, N F7 double-deck roof c
Pontoon roofDouble-deck roof
5011 | 1
10011 | 1
15022 | 2
20032 | 3
25043 | 5
30053 | 7
35064 | d
40074 | d

a This table should not supersede information based on actual tank data.

b If the actual diameter is between the diameters listed, the closest diameter listed should be used. If the actual diameter is midway between the diameters listed, the next larger diameter should be used.

c Roof drains that drain excess rainwater into the product are not used on pontoon floating roofs. They are, however, used on double-deck floating roofs, and are typically left open.

d For tanks more than 300 feet in diameter, actual tank data or the manufacturer's recommendations may be needed for the number of roof drains.